State
Building Operators and Managers Energy Conservation
Action Plan
Immediate
implementation
General
1.
Keep an ongoing record of daily energy consumption.
Recordkeeping will increase energy awareness, help
identify high usage periods and allow measuring the
effectiveness of any energy conservation procedures
that are implemented.
2.
Assign a facility operating staff person the responsibility
of reviewing and approving monthly utility bills.
3.
Involve building tenants in energy conservation efforts.
Ask for their help and ideas about conserving energy.
4.
Try to schedule group activities in the area with
the least energy use, and schedule evening meetings
in areas that can be heated and cooled individually.
This may include offering a work station for staff
people working after hours so they do not need to
heat or cool the entire floor or building for one
person on a weekend.
5.
Schedule teleconferencing whenever possible. Teleconferencing
can reduce energy use and save travel costs.
HVAC
6.
Set heating temperatures at the following maximum
temperatures:
· 68° F to 70° F for all occupied areas
and cafeterias;
· 65° F to 67° F for all lobby corridor
and restroom areas;
· 60° F to 62° F for all building entrances,
storage areas and tunnels;
· Temperature settings for all of the above
referenced spaces must be lowered to 60° F to
62° F during non-working hours;
· 55° F for all unoccupied spaces;
· 55° F for all vacated spaces.
7.
Set cooling temperatures at the following minimum
temperatures:
· 76° F to 78° F for all occupied space
excluding reheat systems;
· Temperatures settings for air-conditioning
turned off or raised to 85° F during nights and
weekends.
Computer
rooms, research facilities and special care facilities
are exempted from the heating and cooling set points
given above. Additional building spaces may be exempted
from all or part of these requirements, pursuant to
the approval of the Commissioner of Administration.
8.
Heating and cooling should start no sooner than 30
minutes before the scheduled building opening time.
9.
Heating and cooling may be set back 30 minutes before
the scheduled building closing time.
10.
Clean or replace air handling unit filters regularly.
Keep outside units free from leaves or debris that
may clog the vent. Dust or vacuum radiator surfaces
frequently to insure a free flow of heat. Make sure
that indoor heating and cooling coils are kept clean.
11.
Verify that the outside air (OSA) dampers are closed
during unoccupied hours, including during morning
warm-up periods. Fresh air is critical while the building
is occupied, but heating OSA when it is not needed
increases energy costs.
12.
Be sure motor-operated dampers are operating properly.
13.
Confirm that the adjustable speed drives (ASD) are
running properly. If they are operating constantly
at maximum speed, they use more energy than the directly
connected motor. Most ASD’s have an output monitor
to report percentage of operation. A motor running
at 50 percent speed uses 1/8 the energy of a motor
running at 100 percent speed.
14.
In the winter, close window coverings at the end of
the day to cut down on heat loss. In the summer, close
window coverings during the day to avoid the heat
gain of direct sunlight, except for conflicts with
day lighting.
15.
Don’t set a higher temperature to “warm
up faster,” or a lower temperature to cool quickly.
It only wastes energy.
16.
Check to make sure that exhaust fans operate only
during occupied periods unless required to operate
continuously.
17.
Check that dampers on exhaust fans close when the
fan is not operating.
18.
Adjust fan belt tension if necessary.
19.
Inspect control schedules and zones so that only the
occupied sections of the building are heated.
20.
Keep drafts away from thermostat to prevent an inaccurate
reading.
21.
Confirm that outside air economizers are functioning
properly to take advantage of free cooling. Most office
buildings are in cooling mode when the outside air
temperature is above 55 degrees F.
22.
Make sure simultaneous heating and cooling does not
occur. Verify proper operation of valves, dampers
and controls.
23.
Monitor boiler stack temperatures on fossil fuel boilers.
If the stack temperature is more than 400 degrees
above the boiler room temperature, schedule the boiler
for a tune-up. Check with your utility provider if
any rebate (incentive) money is available to pay for
the cost of the service.
24.
Turn off circulation pumps during unoccupied times
if no freeze conditions exist.
25.
Check control sequencing for multiple chillers and
boilers. For light load operation, use the smallest
and most efficient chiller or boiler available and
avoid frequent equipment cycling.
26.
Check the duct work for air leaks about once a year
if you have a forced-air heating system. To do this,
feel around the duct joints for escaping air when
the fan is on. Small leaks can be repaired with appropriate
tape. Larger leaks may require caulking.
Lighting
27.
Turn off all lights in unoccupied areas, excluding
emergency lights.
28.
Use natural light whenever possible. Turn off lights
near windows when daylight is adequate.
29.
Make sure photocells (light sensors that turn on electric
lights after dark) are clean.
30.
Use lower wattage bulbs in non-critical areas.
31.
Use the appropriate size wattage for the application.
A 50-watt reflector floodlight provides the same amount
of light as a standard 100-watt bulb.
32.
Use one large bulb instead of several small bulbs
that add up to higher wattage.
33.
Many areas have more lighting than is required for
current tasks. Measure current lighting levels and
reduce excess lighting by using power reducers, multi-level
switching, or simple removal of lamps and ballasts.
Note that some ballasts continue to use energy even
when lamps are not operating.
34.
Ask janitorial services to only light the area of
the building they are working, rather than having
the entire building brightly lit until midnight.
35.
Ask janitorial services to take advantage of partial
switching (such as turning on only one lamp of a three-lamp
fixture, when wired to allow this) to further reduce
energy use during building cleaning.
36.
Avoid using incandescent task light (desk lamps).
Ask your building manager for a compact fluorescent
lamp to replace the incandescent lamp in your task
light.
Water
37.
Watering your landscape wastes electricity along with
water. The water in your home or office gets there
with the use of large electric pumps. Make sure you
follow local watering guidelines for proper landscape
care.
Future implementation
1.
For comprehensive energy efficiency improvements in
existing buildings, agencies can utilize the Department
of Administration’s Guaranteed Energy Savings
program. The program pays for itself from utility
cost savings. Improvements include:
·
Building automation systems
· Carbon dioxide sensors
· Lighting upgrades
· Lighting controls – photocells, occupancy
sensors
· HVAC upgrades
· Water conservation
· Energy efficient windows
2.
If your agency operating budget permits:
·
Replace incandescent bulbs with compact fluorescents,
which can last up to nine times longer.
· Replace the T-12 bulbs with T-8 bulbs with
electronic ballasts.
· Replace incandescent lights in exit signs
with LED fixtures, which can reduce costs of these
signs by up to 95 percent.
· Evaluate water conservation opportunities
such as low flow faucets, low flow toilets and an
evaluation of hand drying methods.
· Install variable speed drives on air handlers.
3.
Consider high efficiency equipment for all new construction
and remodeling upgrades. Most utilities offer rebate
(incentive) programs to pay for the increased cost
of energy efficient equipment.
4.
Confirm that the amount of outside air (OSA) matches
the occupant load. One improvement to consider is
adding carbon dioxide monitors along with controls
that will only bring in as much OSA as necessary for
the current occupant load.
5.
Keep your HVAC systems well tuned with periodic maintenance.
At least once a year have a service technician measure
the carbon dioxide in your gas burner. The higher
the carbon dioxide the greater the efficiency of the
unit. 9% is a good level.
6.
Evaluate central heating and cooling systems for new
and remodel projects. A central heating and cooling
system will use less energy than individual heat-cool
units for most work environments.
7.
Replace failed standard electric motors with higher
efficiency motors. Most electric utilities offer rebate
money to pay for the increased cost of a higher efficiency
motor. Check with your local utility for requirements.
8.
Installing renewable energy systems in buildings may
be cost effective for some buildings and will reduce
the demand on the electric energy system.
9.
Work with utility representatives on energy conservations
measures. Utilize utility programs where applicable.